Water pipes expand or contract for every change of temperature to which they are subjected. To provide for this, in all tall buildings expansion loops are placed in both hot water and circulation pipe to permit the expansion and contraction of the lines without injury to the pipes. The loops are usually from 6 to 8 feet long, made as shown in Fig. 138, placed under floors and spaced about 50 feet apart. Usually hot water and circulation pipes are fastened midway between loops and allowed to expand both up and down. The length that water pipes will expand depends upon the degree to which they are heated and the material of the pipes.

Fig. 138
Within ordinary ranges of temperature, cast iron pipe varies 1/162000 of its length for each degree Fahr., heated or cooled. Wrought iron pipe varies 1/1500000 of its length for each degree Fahr. heated or cooled, and brass pipe varies 1/100000 of its length for each degree Fahr., heated or cooled. Hence the expansion or contraction of any pipe, when the length and the temperature of water are known, can be found by the following rule:
Multiply the length of pipe in inches by the number of degrees Fahr. it is heated or cooled, and divide the product by the coefficient of expansion for the kind of pipe used.
Expressed as a formula: e=1h/ c when 1=length of pipe in inches h=degrees Fahr. the pipe is heated or cooled c=coefficient of expansion (1/ 162000 cast iron, 1/ 1500000 wrought iron and 1/ 100000 brass) e+elongation of pipe in inches
What will be the expansion of a wrought iron pipe 100 feet long when heated from 60 to 212 degrees temperature ?
100 ft.X12 in. X152=182400/ 1500000=1.21 inches.
The following table of linear expansion of cast iron, wrought iron and brass pipe for each 100 feet length at different temperatures, will be found convenient for reference.
Temperature of Air when Pipe is Fitted | Length of Pipe when Fitted | Length of Pipe when heated to | |||||||
215 Deg. Fahr. | 265 Deg. Fahr. | 297 Deg. Fahr. | 338 Deg. Fahr. | ||||||
Deg. Fahr | Feet | Feet | Inches | Feet | Inches | Feet | Inches | Feet | Inches |
0 | 100 | 100 | 1.59 | 100 | 1.96 | 100 | 2.20 | 100 | 2.50 |
32 | 100 | 100 | 1.36 | 100 | 1.65 | 100 | 1.96 | 100 | 2.27 |
64 | 100 | 100 | 1.12 | 100 | 1.43 | 100 | 1.73 | 100 | 2.00 |
Temperature of Air when Pipe is Fitted | Length of Pipe when Fitted | Length of Pipe when heated to | |||
215 Deg. Fahr. | 265 Deg. Fahr. | 297 Deg. Fahr. | 338 Deg. Fahr. | ||
Deg. Fahr. | Feet | Feet Inches | Feet Inches | Feet Inches | Feet Inches |
0 | 100 | 100 1.72 | 100 2.21 | 100 2.31 | 100 2.70 |
32 | 100 | 100 1.47 | 100 1.78 | 100 2.12 | 100 2.45 |
64 | 100 | 100 1.21 | 100 1.61 | 100 1.87 | 100 2.19 |
Temperature of Air when Pipe is Fitted | Length of Pipe when Fitted | Length of Pipe when heated to | |||
215 Deg. Fahr. | 265 Deg. Fahr. | 297 Deg. Fahr. | 338 Deg. Fahr. | ||
Deg. Fahr. 0 32 64 | Feet 100 100 100 | Feet Inches 100 2.58 100 2.19 100 1.81 | Feet Inches 100 3.18 100 2.79 100 2.41 | Feet Inches 100 3.56 100 3.18 100 2.79 | Feet Inches 100 4.05 100 3.67 100 3.28 |
Name | Maker | B. T. U. loss per sq. ft. pipe surface per minute | Per cent. or ratio of loss to loss from bare pipe | Thickness in inches | Weight in ounces per ft. of length, 4 in. diam. |
Nonpareil Cork Standard... | Nonpareil Cork Co | 2.20 | 15.9 | 1.00 | 27 |
Nonpareil Cork Octagonal.. | Nonpareil Cork Co___ | 2.38 | 17.2 | .80 | 16 |
Manville High Pressure..... | Manville Covering Co. | 2.38 | 17.2 | 1.25 | 54 |
Magnesia..................... | Keasby & Mattison Co. H. F. Watson.......... | 2.45 2.49 | 17.7 18.0 | 1.12 1.12 | 35 45 |
Imperial Asbestos | |||||
"W. B."...................... | H. F. Watson.......... Asbestos Paper Co___ Manville Covering Co. | 2.62 2.77 2.80 | 18.9 20 0 20.2 | 1.12 1.12 1.50 | 59 35 |
Asbestos Air Cell............ | |||||
Manville Infusorial Earth... | |||||
Manville Low Pressure | Manville Covering Co. | 2.87 | 20.7 | 1.25 | |
Manville Magnesia Asbestos | Manville Covering Co. | 2.88 | 20.8 | 1.50 | 65 |
Magnabestos................. | Keasby & Mattison Co. | 2.91 | 21.0 | 1.12 | 48 |
Moulded Sectional | H. F. Watson.......... | 3.00 | 21.7 | 1.12 | 41 |
Asbestos Fire Board......... | Asbestos Paper Co___ Philip Carey Co....... | 3.33 | 24.1 | 1.12 | 35 |
Calcite | 3.61 | 26.1 | 1.12 | 66 | |
Bare Pipe | 13.84 | 100. | |||
 